ADDRESS 30
EXIT TIME PROGRAMMING
The EXIT TIME for the ENTRY/EXIT type zones is set in this address. The
EXIT TIME
number of seconds from 01 to 60 is entered. For a time period less than 10 sec
the first digit should be 0.
Each lighting LED includes 10 seconds. For example if the LEDs 1, 2 and 3
light, the chosen time is 20 to 29 seconds.
DEFAULT : 45 seconds
ADDRESS 31
ENTRY TIME PROGRAMMING
The ENTRY time for the ENTRY/EXIT type zones is set in this address. The
ENTRY TIME
number of seconds from 01 to 60 is entered. For a time period less than 10 sec
the first digit should be 0.
Each lighting LED includes 10 seconds. For example if the LEDs 1, 2 and 3
light, the chosen time is 20 to 29 seconds.
DEFAULT : 15 seconds
ADDRESS 32
BELL TIME PROGRAMMING
The bell time period is set in this address. The number of minutes from 1 to 6 is
BELL TIME
entered.
The lighting scale formed by the LEDs from 1 to 6 indicates the period. Each
lighting LED includes 1 minute.
DEFAULT : 3 minutes
ADDRESS 33
BELL DELAY TIME PROGRAMMING
The bell delay time is set in this address. The number of minutes from 1 to 6 is
BELL DELAY
entered.
The lighting scale formed by the LEDs from 1 to 6 indicates the period. Each
lighting LED includes 1 minute.
DEFAULT : 0 minutes
CA60Plus

3. TIMES

The lighting scale formed by the LEDs from 1 to 6 indicates the period.
The lighting scale formed by the LEDs from 1 to 6 indicates the period.
19
Installation Manual