806f0a07-0302ffff
[ProcessorElementName] is operating in a Degraded State.
Explanation: The processor 2 is being throttled due to thermal or power conditions.
Severity: Warning
Alert Category: Warning - CPU
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0038
SNMP Trap ID: 42
Automatically notify Support: No
User response: Check the IMM event log for any fan, cooling, or power related issues.
For a thermal condition:
1. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
2. Make sure that the room temperature is within operating specifications.
For a power condition:
1. If Power Supply Unit is rated 1400 Watt, Make sure it is connected to 220V AC input
2. If using a 900 Watt rated power supply (connected at either 110V or 220 V ), may need to upgrade to a 1400 Watt
rated power supply (connected at 220V).
806f0a07-0303ffff
[ProcessorElementName] is operating in a Degraded State.
Explanation: The processor 3 is being throttled due to thermal or power conditions.
Severity: Warning
Alert Category: Warning - CPU
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0038
SNMP Trap ID: 42
Automatically notify Support: No
User response: Check the IMM event log for any fan, cooling, or power related issues.
For a thermal condition:
1. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
2. Make sure that the room temperature is within operating specifications.
For a power condition:
1. If Power Supply Unit is rated 1400 Watt, Make sure it is connected to 220V AC input
2. If using a 900 Watt rated power supply (connected at either 110V or 220 V ), may need to upgrade to a 1400 Watt
rated power supply (connected at 220V).
806f0a07-0302ffff • 806f0a07-0303ffff
Appendix D. Integrated management module II (IMM2) error messages
531