80010b01-1403ffff • 80010b01-1404ffff
80010b01-1403ffff
Numeric sensor [NumericSensorElementName] going high (upper non-recoverable) has
asserted.
Explanation: The temperature for a system board voltage regulator has risen above its threshold. A hard shutdown
has occurred.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0498
SNMP Trap ID: 0
Automatically notify Support: No
User response:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80010b01-1404ffff
Numeric sensor [NumericSensorElementName] going high (upper non-recoverable) has
asserted.
Explanation: The temperature for a system board voltage regulator has risen above its threshold. A hard shutdown
has occurred.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0498
SNMP Trap ID: 0
Automatically notify Support: No
User response:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
410
System x3750 M4 Types 8722 and 8733: Installation and Service Guide