80010b01-2701ffff
Numeric sensor [NumericSensorElementName] going high (upper non-recoverable) has
asserted.
Explanation: The ambient temperature has risen above its threshold. A hard shutdown has occurred.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0498
SNMP Trap ID: 0
Automatically notify Support: No
User response:
1. Check event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
80010b01-2d01ffff
Numeric sensor [NumericSensorElementName] going high (upper non-recoverable) has
asserted.
Explanation: The PCH temperature sensor has risen above its threshold. A hard shutdown has occurred.
Severity: Error
Alert Category: Critical - Temperature
Serviceable: Yes
CIM Information: Prefix: PLAT and ID: 0498
SNMP Trap ID: 0
Automatically notify Support: No
User response:
1. Check the IMM event log for any fan or cooling related issues.
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are in place and
correctly installed.
3. Make sure that the room temperature is within operating specifications.
4. If this is the only temperature related event and the event persists, replace the system board (Trained Service
personnel only).
80010b01-2701ffff • 80010b01-2d01ffff
Appendix D. Integrated management module II (IMM2) error messages
415