16.46 Yokogawa PLC Series [PDS]

16.46.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
PLC Type
Serial I/F port
Baud rate
Parity
Data bits
Stop bits
HMI station No.
PLC station No.
Comm. delay (10msec) 0
16.46.2 PLC Setting
Communication parameters must be the same as those of the MMI. Additionally, Select Use Personal Communication
Link, Use checksum, and Use End Character.
Compatible with:
Yokogawa: FA-M3 series
16.46.3 Wiring
16.46.3.1
Wiring for cable connections using FA-M3 series CPUs with RS232 D-Sub 9 Male Socket ports.
KEP Part#: ZA9M9F (D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
Note: Graphic representation may not reflect the actual appearance of the finished cable.
Recommended Setting Notes
YOKOKAWA Series
[PDS V1.04]
RS-232
19200
Even
8
1
0
1
Connect to VIGOR: M Series, V Series, VB Series CPU RS-232 port
2 RD
3 TD
5 GND
Shield
Earth Ground
Yokogawa.pds driver must be present in \drivers folder
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not Used
Options: 0~255 - Must match PLC setting
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.