16.34 OMRON CQM1H-CPU61 [PDS]

16.34.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
PLC Type
[pds]OMRON CQM1H-
CPU61
Serial I/F port
RS-232, RS485 2W
Baud rate
9600
Parity
Even
Data bits
7
Stop bits
2
HMI station No.
0
PLC station No.
0
Comm. delay (10msec) 0
[pds]OMRON CQM1H-CPU61 Ver1.00 supports Extended Address mode.
16.34.2 PLC Setting
Host Link Protocol Communication parameters must be the same as those of the HMI
Set Station Number as "00" if not using Extended Address mode or RS232 connections.
Compatible with:
CQM1 Series: CQM1H-CPU61, CQM1H-SCB41
CPM1H Series: SCB41
16.34.3 Wiring
16.34.3.1
Wiring for cable connections using OMRON CQM1H-CPU61 CPU with RS-232 Host Link D-Sub 9
Female Plug ports.
KEP Part#: SMICOMCQM-05 (D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
9
7 RTS
8 CTS
Omron.pds driver must be present in \drivers folder
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Options: 9600, 19200 - Must match PLC port setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Options: 0-255 - As per PLC setting if not using Extended Addressing
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Connect to OMRON CQM1H-CPU61 CPU RS-232 Host Link port
3 RD
2 TD
9 GND
4 RS
5 CS
1
Shield
Earth Ground