16.45 VIGOR M Series

16.45.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Serial I/F port
Baud rate
Parity
Data bits
Stop bits
HMI station No.
PLC station No.
Comm. delay (10msec) 0
16.45.2 PLC Setting
Communication parameters must be the same as those of the MMI
Compatible with:
VIGOR: M Series, V Series, VB Series
16.45.3 Wiring
16.45.3.1
Wiring for cable connections using M Series, V Series, VB Series CPU with RS422 Screw Terminal
ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to Flying Leads Cable)
HMI PLC[RS-485]
2 RXD+
1 RXD-
4 TXD+
3 TXD-
5 GND
Recommended Setting Notes
RS-232, RS-485(4W)
19200
Even
7
1
0
1
Connect to M Series, V Series, VB Series CPU RS422 Port
1 TXD-
2 TXD+
3 RXD-
4 RXD+
5 GND
Shield
Earth Ground
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not Used
Options: 0~255 - Must match PLC setting
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
295