Omron Cs/Cj Ver 1.00A; Omron Cs/Cj [Pds] - KEP MMI-1500 Installation & Operation Manual

Mmi-touchscreen series
Table of Contents

Advertisement

16.35 OMRON CS/CJ [PDS]

16.35.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
OMRON CS/CJ Ver 1.01b OmronCS_CJ.pds driver must be present in \drivers folder
PLC Type
Serial I/F port
RS-232, RS485 2W
Baud rate
9600
Parity
Even
Data bits
7
Stop bits
2
HMI station No.
0
PLC station No.
0
Comm. delay (10msec) 0
Parameter 6
0
16.35.2 PLC Setting
Host Link Protocol Communication parameters must be the same as those of the HMI
Compatible with:
CS1Series: CS1G-CPU42EV1, 43EV1, 44EV1, 45EV1; CS1H-CPU63EV1, 64EV1, 65EV1, 66EV1, and 67EV1
CS1H Series: CS1G-CPU42H, 43H, 44H, 45H; CS1H-CPU63H, 64H, 65H, 66H, and 67H
CJ1 Series: CJ1G-CPU42, 43, 44, 45; CJ1H-CPU65, 66; CJ1W-SCU41
16.35.3 Wiring
16.35.3.1
Wiring for cable connections using OMRON CS1 and CJ1 Series CPUs with RS-232 Host Link D-
Sub 9 Female Plug ports.
KEP Part#: SMICOMCQM-05 (D-Sub 9 Male Socket to D-Sub 9 Male Socket Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
9
7 RTS
8 CTS
Notes
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC
hardware
Options: 9600, 19200 - Must match PLC port setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Not used
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Error Report Register
This Parameter is the LW register number to hold any returned errors
from the OMRON CS/CJ controller. (For example: Setting this
parameter to 100, activates LW0100 as the error code register.)
Note: Setting this parameter to 0 disables error reporting.
Connect to OMRON CS1 or CJ1 CPU RS-232 Host Link port
3 RD
2 TD
9 GND
4 RS
5 CS
1
Shield
Earth Ground
280

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmi-750Mmi-730Mmi-850

Table of Contents