16.20 LG Master K10S1

16.20.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Serial I/F port
RS232
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1
HMI station No.
0
PLC station No.
1
Comm. delay (10msec) 0
16.20.2 PLC Setting
Communication parameters must be the same as those of the MMI.
Compatible PLCs:
LG MASTER-K Series K10S1
16.20.3 Wiring
16.20.3.1
Wiring for cable connections using LG MASTER-K Series K10S1 CPU's with RS232 D-Sub 9 Male
Socket ports.
KEP Part#: ZA9M9F (D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
2 TXD
3 RXD
5 GND
Note: Graphic representation may not reflect the actual appearance of the finished cable.
Connect to LG MASTER-K K10S1 CPU RS-232 port
2 RXD
3 TXD
5 GND
Shield
Earth Ground
Notes
Options: RS232
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Not used
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
243