16.26 MITSUBISHI A1S, A2A, A2US, A3N/A1SH

16.26.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
PLC Type
Serial I/F port
Baud rate
Parity
Data bits
Stop bits
HMI station No.
PLC station No.
Comm. delay (10msec) 0
16.26.2 PLC Settings
Communication parameters must be the same as those of the MMI.
Compatible with:
Mitsubishi A Series: A1S, A2A, A2US and A3N/A1SH
16.26.3 Wiring
Use KEP Part#: 500_AnS cable to connect HMI RS-232 port with Mitsubishi A Series CPU port.
Cable wiring not available.
16.26.4 Device address
Bit/Word
Type
Address Format
B
X
B
Y
B
M
B
B
B
F
W
TV
W
CV
W
D
W
W
W
R
Note: The PLC's memory range may vary within the range supported by the driver. Use appropriate addresses.
Recommended Setting Notes
MITSUBISHI A1S
MITSUBISHI A2A
MITSUBISHI A2US
MITSUBISHI A3n/A1SH
RS232
9600
Odd
8
1
0
0
Range
hhhh
hhh: 0~FFFF
hhhh
hhh: 0~FFFF
ddddd
ddddd: 0~65535
hhhh
hhhh: 0~ FFFF
ddddd
ddddd: 0~65535
ddddd
ddd: 0~65535
ddddd
ddd: 0~65535
ddddd
dddd: 0~65535
hhhh
hhhh: FFFF
ddddd
ddd: 0~65535
Must match PLC port setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Not used
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Input Relays, Addresses are in hexadecimal
Output Relays, Addresses are in hexadecimal
Auxiliary Relays
Addresses are in hexadecimal
Note: Not Available for A2US
Note: Not Available for A2US
Timer Accumulator
Counter Accumulator
Data Registers
Addresses are in hexadecimal.
Note: Not Available for A2US
Note: Not Available for A2US
255