16.24 Matsushita FP (Aromat)

16.24.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Serial I/F port
Baud rate
Parity
Data bits
Stop bits
HMI station No.
PLC station No.
Comm. delay (10msec) 0
16.24.2 PLC Setting
Communication parameters must be the same as those of the MMI.
Compatible with:
FP Sigma, FP0, FP1, FP2, FP2SH, FP10SH and FP3
16.24.3 Wiring
16.24.3.1
Wiring for cable connections using Matsushita FP1 CPU's with Hirose MiniDIN RS422 ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to Hirose MiniDIN 8 Male Cable)
HMI PLC[RS-485]
1 RXD-
2 RXD+
3 TXD-
4 TXD+
5 GND
16.24.3.2
Wiring for cable connections using Matsushita FP Sigma, FP0, FP2, FP2SH,
FPM CPU's with RS232 MiniDIN 5 ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to MiniDIN 5 Male Cable)
HMI PLC[RS-232]
2 RXD
3 TXD
5 GND
Recommended Setting Notes
RS232
9600
Odd
8
1
0
1
Connect to Matsushita FP1 CPU Port
5 TXA-
2 TXB+
3 RXA-
6 RXB+
1 GND
Shield
Earth Ground
Connect to Matsushita FP Sigma, FP0, FP2, FP2SH or FPM CPU Port
5 TXD
3 RXD
1 GND
Shield
Earth Ground
Options: RS232, RS485 – Dependant on PLC hardware
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Options: Odd, Even, None - Must match PLC port setting
Options: 7, 8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Must match PLC port setting (0-255) Note: FP3 must set 0
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
249