Samsung Spc-10 - KEP MMI-1500 Installation & Operation Manual

Mmi-touchscreen series
Table of Contents

Advertisement

16.37 Samsung SPC-10

16.37.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
Serial I/F port
RS485 2W
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1
HMI station No.
192
PLC station No.
255
Comm. delay (10msec) 0
16.37.2 PLC Setting
Communication parameters must be the same as those of the MMI
Compatible with:
Samsung SPC-10
16.37.3 Wiring
16.37.3.1
Wiring for cable connections using Samsung SPC-10 CPU with RS485 Round 8 pin MiniDIN ports.
KEP Part#: (Not Available) (D-Sub 9 Female Plug to 8 pin MiniDIN Male Plug Cable)
HMI PLC[RS-485]
1 RXD/TXD-
2 RXD/TXD+
5 GND
Note: Graphic representation may not reflect the actual appearance of the finished cable.
16.37.4 Device address
Bit/Word
Type
Address Format
B
R
B
K
B
M
B
F
W
W
Must match PLC port setting
Must match PLC port setting
Must match PLC port setting
Must match PLC port setting
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Connect to Samsung SPC-10 CPU's RS-485 Port
6 RXD/TXD-
7 RXD/TXD+
5 GND
Shield
Earth Ground
Range
dddd(dd)
dddd: 0~9999 (dd): 0~15
dddd(dd)
dddd: 0~9999 (dd): 0~15
dddd(dd)
dddd: 0~9999 (dd): 0~15
dddd(dd)
dddd: 0~9999 (dd): 0~15
dddd
dddd: 0~9999
Notes
Input / Output
Keep relay
Internal relay
Special relay
Data register
284