10.3.2 Reserved Local Words

LW Address
Description
9000
Retentive memory Index base
9002-9003
Set to Numeric Input Maximum value
when numeric input gets the focus.
9004-9005
Set to Numeric Input Minimum value when
numeric input gets the focus.
9006
Message board mode
0: pen
1: brush
2: clipping
9007
Pen width
0:1 pixel
1:2 pixel
2:3 pixel
9008
Pen color
0-255
9010
Local second
9011
Local minute
9012
Local hour
9013
Local day
9014
Local month
9015
Local year
9016
Local day of the week
9020
Object queue status
This holds the total number of objects of all
the windows on the display.
(Each window can hold up to 500 objects.)
9034-9035
System time (unit as 0.1 second)
9040-9041
Window Security password
This word must contain the password for
access to secure windows.
9042
Security level
The current active security level
9043
Force security level
Set to 0 (Lowest) or 1 (Middle).
NOTE
RBI and RWI use this as an index offset when
accessing retentive data. (read/write)
Numeric Input loads its maximum value when
activated. When Numeric Input loses the
focus, it is set to zero.
(read only)
Numeric Input loads its minimum value when
activated. When Numeric Input loses the
focus, it is set to zero.
(read only)
Message board use
(read)
Message board use
(read)
Message board use
(read/write)
BCD code, valid values: 0 ~ 59
(read/write allow)
BCD code, valid values: 0 ~ 59
(read/write allow)
BCD code, valid values: 0 ~ 23
(read/write allow)
BCD code, valid values: 0 ~ 31
(read/write allow)
BCD code, valid values: 0 ~ 11
(read/write allow)
BCD code, valid values: 0 ~ 9999
(read/write allow)
BCD code, valid values: 0 ~ 6
(read/write allow)
If a screens object queue exceeds 1000, then
the HMI screen is too complex. The HMI is in
danger of reporting a Severe System Error
due to low system resources.
Starts at 0 when project started. (read/write)
Double word
(write only)
(read only)
A security level can only be forced to a lower
level than is active. (write only)
102
Version
Ver 1.2
Ver 1.4
Ver 1.4
Ver 1.4
Ver 1.4
Ver 1.4
Ver 1.2
Ver 1.2
Ver 1.2
Ver 1.2
Ver 1.2
Ver 1.2
Ver 1.2
Ver 1.4
Ver 1.4
Ver 1.6
Ver 1.6
Ver 1.6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmi-750Mmi-730Mmi-850

Table of Contents