16.32 MODBUS RTU TCP/IP

16.32.1 HMI Setting – Ethernet port hardware option must be present
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Serial I/F port
HMI station No.
PLC station No.
Comm. delay (10msec)
Multiple HMI
Connect I/F
Local IP address
Server IP address
Subnetwork Mask
Default Route IP address
16.32.2 PLC Setting
PLC ID number must match setting in MMI
16.32.3 Wiring
Use the same wiring as the MODBUS RTU driver. CAT-5 class through cable to Hub or crossover cable to Controller.
16.32.4 Device address
Bit/Word
Type
Address Format
B
1x
B
0x
B
3x_bit
B
4x_bit
W
3x
W
4x
W
5x
Note: The Controller's memory range may vary within the range supported by the driver. Use appropriate addresses.
NOTE:
Address type "5x" is mapped to 4x Internal Registers. 5x register types are the same as "4x" except "5x" double word data
is swapped.
For example,
If 4x has the following information
Address
1
Data in word
0x123
4x Data
0x2670123
For 5x, it becomes
Address
1
Data in word
0x123
5x Data
0x1230267
Recommended Setting Notes
Ethernet
0
1
0
Master
Ethernet
ddddd
ddddd: 1~9999
ddddd
ddddd: 1~9999
ddddbb
dddd: 1~9999 bb: 0~15
ddddbb
dddd: 1~9999 bb: 0~15
ddddd
ddddd: 1~9999
ddddd
ddddd: 1~9999
ddddd
ddddd: 1~9999
2
3
0x267
0x3
0x40003
2
3
0x267
0x3
0x30004
Not used
Options: 0-255 - As per PLC setting
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
The IP address of the HMI unit
The IP address of the PLC
IP Mask
The IP address of the main server
Range
Input bits (Read only)
Internal Coils
Internal Input Coils (Read only)
Internal Register Coils
Input Registers (Read only)
Internal Registers
4x type with Double Words swapped
4
5
0x4
0x5
0x5
4
5
0x4
0x5
0x50000
274
Notes
6
0x0
6
0x0