16.10 GE Fanuc SNP-X

16.10.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Serial I/F port
Baud rate
Parity
Data bits
Stop bits
HMI station No.
PLC station No.
Comm. delay (10msec) 0
16.10.2 PLC Setting
Communication parameters must be the same as those of the MMI. Protocol is SNP-X.
The Modem Turnaround Delay must be set to 0.
The Level 2 Password in the PLC must be set to NULL
Compatible PLCs
• Series 90-30: 311, 313, 323, 331, 340, 341, 351, 363, 364, CMM311
• Series 90-70: 731, 771, 772, 780, 781, 782, 788, 789, 790, 915, 925, CSE784, CSE924, CMM711
• Series 90 Micro: IC693UDR001, IC693UDR002, IC693UAA003, IC693UDR005, IC693UAL006, IC693UAA007,
IC693UDR010
• VersaMax: CPU001, CPU002, CPU005, CPU E05
NFORMATION
16.10.3 Wiring
16.10.3.1
Wiring for cable connections using GE 90/30 Series and VersaMax CPU's with RS422 D-Sub 15
Female Plug ports.
KEP Part#: SMIC15GE90-05 (D-Sub 9 Female Plug to D-Sub 15 Male Socket Cable)
HMI PLC[RS-485]
1 RXD-
2 RXD+
3 TXD-
4 TXD+
5 GND
Recommended Setting
RS-485
19200
Odd
8
1
0
0
Connect to GE 90 Series CPU's with RS422 Port
12 SD(A)
13 SD(B)
10 RD(A)
11 RD(B)
9 RT
7 SG
6 RTS(A)
15 CTS(A)
14 RTS(B)
8 CTS(B)
1
Shield
Earth Ground
Notes
Options: RS232, RS485 – Dependant on PLC hardware
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Options: Odd, Even, None - Must match PLC port setting
8 - Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not used
Not used
Request delay: 0~999 @10 milliseconds. Use when the PLC requires
a delay between requests. Not implemented in simulation mode.