Toshiba T Serial - KEP MMI-1500 Installation & Operation Manual

Mmi-touchscreen series
Table of Contents

Advertisement

16.44 Toshiba T Serial

16.44.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting Notes
Serial I/F port
RS-232, RS-485(4W)
Baud rate
9600
Parity
Odd
Data bits
8
Stop bits
1
HMI station No.
0
PLC station No.
1
Comm. delay (10msec) 0
This driver supports Extended Address mode.
16.44.2 PLC Setting
Communication parameters must be the same as those of the MMI. Set PLC node ID.
Compatible with:
Toshiba T Series: T1, T2, T2E, T2N, T3, T3H, S2T
16.44.3 Wiring
16.44.3.1
Wiring for cable connections using Toshiba T1 Series CPU's with RS232 Round 8 pin MiniDIN
ports.
KEP Part#: SMICTSBT1-05 (D-Sub 9 Male Socket to 8 pin MiniDIN Male Plug Cable)
HMI PLC[RS-232]
2 TXD
3 RXD
5 GND
9
16.44.3.2
Wiring for connections using Toshiba T2/T3 Series CPU's with RS232 D-Sub 9 Female Plug ports.
KEP Part#: (Not Available) (D-Sub 9 Male Socket to D-Sub 9 Male Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
Options: RS-232, RS-485 default/2W/4W – Dependant on PLC hardware
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC port
setting
Options: Odd, Even, None - Must match PLC port setting
Must match PLC port setting
Options: 1, 2 - Must match PLC port setting
Not Used
Must match PLC port setting (0~255)
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.
Connect to Toshiba T1 Series CPU's with RS232 Port
8 RXD
6 TXD
3 GND
4 RTS
7 CTS
Shield
Earth Ground
Connect to Toshiba T2/T3 Series CPU's with RS232 Port
2 RD
3 TD
5 GND
7 RTS
8 CTS
Shield
Earth Ground