Pds]Fuji Nb Series Ver1.0; Fuji Nb Series [Pds] - KEP MMI-1500 Installation & Operation Manual

Mmi-touchscreen series
Table of Contents

Advertisement

16.9 FUJI NB Series [PDS]

16.9.1 HMI Setting
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
PLC type
FUJI NB Series [PDS V1.00]
Serial I/F port
RS-485
Baud rate
19200
Parity
Odd
Data bits
8
Stop bits
1
HMI station No.
0
PLC station No.
0
Parameter 1
0
Comm. delay (10msec) 0
16.9.2 Fuji Settings
Communication parameters must be the same as those of HMI (See recommendation above).
Compatible with:
FUJI NB0 and NB1 Series
16.9.3 Wiring
16.9.3.1
Wiring for cable connections using Fuji NB CPU's with RS422 RJ-45 Socket ports.
KEP Part#: (Not Available) (D-Sub 9 Female Socket to RJ-45 Female Plug Cable)
HMI PLC[RS-485]
1 RXD-
2 RXD+
3 TXD-
4 TXD+
5 GND
Note: Graphic representation may not reflect the actual appearance of the finished cable.
16.9.4 Device address
Bit/Word
Type
B
Y
B
X
B
M
B
L
B
C
B
M_Spe*
B
T
W
CV
W
TV
W
D
W
D_Spe*
Note: *M_Spe and D_Spe ranges begin at 8000. However, the Device Address is only the last three digits of the full
address. (Example: A numeric display is to show D8015. The Device type selection is D_Spe, the Device Address is 15.)
Note: The PLC's memory range may vary within the range supported by the driver. Use appropriate addresses.
Connect to Fuji NB CPU with RS422 Port
4 TXD-
3 TXD+
6 RXD-
5 RXD+
2 or 8 GND
Shield
Earth Ground
Addressing format
Range (NB0) Note
hh (Hexadecimal)
hh: 0~1F
hh
hh: 0~1F
hhh
hh: 0~FF
hhh
hh: 0~0FF
hhh
hh: 0~01F
hhh
hhh: 0~1FF
hh
hh: 0~1F
hh
hh: 0~1F
hh
hh: 0~1F
hh
hh: 0~1F
hh
hh: 0~3F
Notes
FujiNB.pds driver must be present in \drivers folder
Must match PLC setting
Must match PLC setting
Must match PLC setting
Must match PLC setting
Not used
The Station number must match the PLC Station Number (0-255)
PLC Password (default is 0)
Request delay: 0~999 @10 milliseconds. Use when the PLC
requires a delay between requests. Not implemented in simulation
mode.
Output Relay
Output Relay
Internal Relay
Latch Relay
Counter
Special Relay
Timer
Counter value
Timer value
Data Register
Special Register
222

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmi-750Mmi-730Mmi-850

Table of Contents