16.1 AB DF1

16.1.1 HMI Settings
Communication parameters must be set the same as those of the PLC. The following settings are recommended.
Parameter
Recommended Setting
Serial I/F port
RS-232
Baud rate
19200
Parity
None
Data bits
8
Stop bits
1
HMI station No.
0
PLC station No.
1
Comm. delay (10msec) 0
16.1.2 PLC Setting
Supports all SLC Series PLC's that have DF1 ports.
Communication parameters must be the same as those of the MMI.
Full Duplex Operation must be set.
No Hardware Handshaking must be set.
16.1.3 Wiring
16.1.3.1
Wiring for cable connections using AB Micrologix CPU's with RS232 Round 8 pin MiniDIN ports.
KEP Part#: SMICABMICRO-05 (D-Sub 9 Male Socket to 8 pin MiniDIN Male Plug Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
9
16.1.3.2
Wiring for cable connections using AB CompactLogix or ControlLogix CPU's with RS232 D-Sub
9 Male Socket ports.
KEP Part#: SMICABDF1-05 (D-Sub 9 Male Socket to D-Sub 9 Female Plug Cable)
HMI PLC[RS-232]
2 TD
3 RD
5 GND
9
Connect to AB Micrologix 1000, 1200, 1500 CPU's RS-232 Port
4 RX
7 TX
2 GND
Shield
Earth Ground
Connect to AB Micrologix 1500, SLC5/03 or SLC5/04 CPU RS-232 port
2 RD
3 TD
5 GND
7 RTS
8 CTS
Shield
Earth Ground
Notes
Options: RS232, RS485 – Dependant on PLC hardware
Options: 9600, 19200, 38400, 57600, 115200 - Must match PLC channel
setting
Options: Odd, Even, None - Must match PLC channel setting
Options: 7, 8 - Must match PLC channel setting
Options: 1, 2 - Must match PLC channel setting
HMI station No. must be 0
The Station number must match the PLC Node Number (0-31)
Request delay: 0~999 @10 milliseconds. Use when the PLC requires a
delay between requests. Not implemented in simulation mode.