Using Intelligent Output Terminals
4-6-5
Run Signal
228
When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it
is in Run Mode. The output logic is active
low, and is the open collector type
(switch to ground).
Option
Terminal
Code
Symbol
RUN
Run Signal
Valid for inputs:
11, 12, AL0 - AL2
Required settings:
(none)
Notes:
• The inverter outputs the [RUN] signal when-
ever the inverter output exceeds the start fre-
quency specified by parameter . The
start frequency is the initial inverter output fre-
quency when it turns ON.
• The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent
the negative going turn-off spike generated by
the coil from damaging the inverter's output
transistor.
[FW,RV]
Output
frequency
Run
signal
Function
State
Name
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Example for terminal [11] (default
output configuration shown – see
page 158):
Example for terminal [AL0],
[AL1], [AL2] (requires output
configuration – see page 226
and page 158):
See I/O specs on page 195
Section 4-6
1
0
b082
start freq.
1
ON
0
Description
Inverter output
terminal circuit
RUN
CM2
11
RY
Inverter logic
RUN
circuit board
AL0
AL1
AL2
Power
Load
supply