Run Signal - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

Using Intelligent Output Terminals
4-6-5

Run Signal

228
When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it
is in Run Mode. The output logic is active
low, and is the open collector type
(switch to ground).
Option
Terminal
Code
Symbol

RUN
Run Signal
Valid for inputs:
11, 12, AL0 - AL2
Required settings:
(none)
Notes:
• The inverter outputs the [RUN] signal when-
ever the inverter output exceeds the start fre-
quency specified by parameter . The
start frequency is the initial inverter output fre-
quency when it turns ON.
• The example circuit for terminal [11] drives a
relay coil. Note the use of a diode to prevent
the negative going turn-off spike generated by
the coil from damaging the inverter's output
transistor.
[FW,RV]
Output
frequency
Run
signal
Function
State
Name
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Example for terminal [11] (default
output configuration shown – see
page 158):
Example for terminal [AL0],
[AL1], [AL2] (requires output
configuration – see page 226
and page 158):
See I/O specs on page 195
Section 4-6
1
0
b082
start freq.
1
ON
0
Description
Inverter output
terminal circuit
RUN
CM2
11
RY
Inverter logic
RUN
circuit board
AL0
AL1
AL2
Power
Load
supply
t