Motor Cooling Rate; Reduced Torque; Constant Torque; Free Setting - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

"B" Group: Fine Tuning Functions
Reduction rate
x1.0
x0.8
x0.6
Reduction rate
x1.0
x0.8
3-6-3-2

Motor Cooling Rate

• Reduced Torque (=)
Example:
0
5
16
50
0
6
20
60
Base FQ
Output frequency [Hz]
• Constant Torque =)
Example:
0
3
60
Output frequency [Hz]
• Free setting ()
Reduction rate
x1.0
x0.8
Setting range
0
3
Output frequency [Hz]
• Several cooling patterns are added
If b910 is set to zero exactly the same model than inverter will be used.
The other options allow to adjust the cooling ramp on a better way and avoid
the overload detection in some cases where really the motor is not getting hot.
3G3MX2-A2015**, Base FQ=60Hz,
60Hz (Reduction rate: x1.0)
Trip time
[s]
60
0.5
0
11.1
11.5
(116%)
(120%)
Motor current [A]
3G3MX2-AB015**, Base FQ=60Hz,
60Hz (Reduction rate: x1.0)
Trip time
[s]
60
3.0
0
8.72
12.0
16.0[A]
(109%)
(150%)
(200%)
Motor current [A]
400
Section 3-6
ND setting (Rated current 9.6A= b012)
20Hz (Reduction rate: x0.8)
Trip time
[s]
60
0.5
0
14.4[A]
8.9
(150%)
(92.8%)
Motor current [A]
HD setting (Rated current 8.0A= b012)
3Hz (Reduction rate: x0.8)
Trip time
[s]
60
3.0
0
7.0
(87.2%)
(120%)
Motor current [A]
Output current [A]
b020
b018
b016
0
b015
b017
b019
Output frequency [Hz]
9.2
11.5[A]
(96%)
(120%)
9.6
12.8[A]
(160%)
A004 Max. FQ