Input Function Summary Table - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

"C" Group: Intelligent Terminal Functions
Option
Terminal
Code
Symbol

FW

RV

CF1 *1

CF2

CF3

CF4

JG

DB

SET

2CH

FRS

EXT

USP

CS

SFT

AT

RS
Input Function Summary Table - This table shows all intelligent input func-
tions at a glance. Detailed description of these functions, related parameters
and settings, and example wiring diagrams are in 4-5 Using Intelligent Input
Terminals on page 201.

Input Function Summary Table

Function Name
Forward Run/Stop
ON
OFF
Reverse Run/Stop
ON
OFF
Multi-step speed
ON
setting binary 1
OFF
Multi-step speed
ON
setting binary 2
OFF
Multi-step speed
ON
setting binary 3
OFF
Multi-step speed
ON
setting binary 4
OFF
Jogging
ON
OFF
External DC injection
ON
braking
OFF
nd
Set (select) 2
motor
ON
Data
OFF
2-step acceleration/
ON
deceleration
OFF
Free-run stop
ON
OFF
External trip
ON
OFF
Unattended start
ON
protection
OFF
Commercial switch
ON
OFF
Soft lock
ON
OFF
Analog input switching
ON
OFF
Reset
ON
OFF
Description
Inverter is in Run Mode, motor runs forward
Inverter is in Stop Mode, motor stops
Inverter is in Run Mode, motor runs reverse
Inverter is in Stop Mode, motor stops
Binary encoded speed select, Bit 0, logical 1
Binary encoded speed select, Bit 0, logical 0
Binary encoded speed select, Bit 1, logical 1
Binary encoded speed select, Bit 1, logical 0
Binary encoded speed select, Bit 2, logical 1
Binary encoded speed select, Bit 2, logical 0
Binary encoded speed select, Bit 3, logical 1
Binary encoded speed select, Bit 3, logical 0
Inverter is in Run Mode, output to motor runs at jog
parameter frequency
Inverter is in Stop Mode
DC braking will be applied during deceleration
DC braking will not be applied
nd
The inverter uses 2
motor parameters for generat-
ing frequency output to motor
The inverter uses 1st (main) motor parameters for
generating frequency output to motor
Frequency output uses 2nd-stage acceleration and
deceleration values
Frequency output uses standard acceleration and
deceleration values
Causes output to turn OFF, allowing motor to free
run (coast) to stop
Output operates normally, so controlled deceleration
stop motor
When assigned input transitions OFF to ON, inverter
latches trip event and displays E 12
No trip event for ON to OFF, any recorded trip events
remain in history until reset
On powerup, the inverter will not resume a Run com-
mand
On powerup, the inverter will resume a Run com-
mand that was active before power loss
Motor can be driven by commercial power
Motor is driven via the inverter
The keypad and remote programming devices are
prevented from changing parameters
The parameters may be edited and stored
Refer to Analog Input Settings on page 93.
The trip condition is reset, the motor output is turned
OFF, and powerup reset is asserted
Normal power-ON operation
Section 3-7
155