Using Intelligent Input Terminals
4-5-7

Reset

!WARNING
210
Use weak-current type relays for FWY, RVY, and CSY. The figures below
show the sequence and timing of operations for reference.
Switching from inverter to commercial power
ON
MC1
MC2
ON
MC3
ON
FW
ON
CS
ON
Inverter
Operation
output freq.
If the inverter trips because of overcurrent when it starts the motor with fre-
quency matching, increase the retry wait time before motor starts (
Option
Terminal
Code
Symbol

CS
Commercial
switch
~
Valid for inputs:
, 
Required settings:
Notes:
inverter may start the motor with 0 Hz if:
• the motor speed is no more than half of the base frequency, or
• the voltage induced on the motor is attenuated quickly.
The [RS] terminal causes the inverter to execute the reset operation. If the
inverter is in Trip Mode, the reset cancels the Trip state. When the signal [RS]
is turned ON and OFF, the inverter executes the reset operation.
After the Reset command is given and the alarm reset occurs, the motor will
restart suddenly if the Run command is already active. Be sure to set the
alarm reset after verifying that the Run command is OFF to prevent injury to
personnel.
Option
Terminal
Code
Symbol

RS
Reset
~
Valid for inputs:
Required settings:
(none)
Switching from commercial power to inverter
MC1
MC2
ON
MC3
FW
CS
Inverter
0.5 to 1 s
output freq.
Function
State
Name
ON
OFF
Function
State
Name
ON
The motor output is turned OFF,
the Trip Mode is cleared (if it
exists), and powerup reset is
applied
OFF
Normal power ON operation
Section 4-5
ON
Duration of the interlock of
MC2 and MC3 (0.5 to 1 s)
ON
ON
ON
Retry wait time
b003
Start with freq. matching

).
Description
Description