ModBus Data Listing

Parameter group C

Register
Function name
No.
1401h
Multi-function input 1 selection
1402h
Multi-function input 2 selection
1403h
Multi-function input 3 selection
1404h
Multi-function input 4 selection
1405h
Multi-function input 5 selection
1406h
Multi-function input 6 selection
1407h
Multi-function input 7 selection
1408h to
(Reserved)
140Ah
140Bh
Multi-function input 1 operation
selection
140Ch
Multi-function input 2 operation
selection
140Dh
Multi-function input 3 operation
selection
332
Function
R/W
Monitoring and setting items
code
C001
R/W
00 (FW: Forward RUN), 01 (RV: Reverse
RUN), 02 (CF1: Multispeed 1 setting), 03
(CF2: Multispeed 2 setting), 04 (CF3:
Multispeed 3 setting), 05 (CF4: Multi-
speed 4 setting), 06 (JG: Jogging), 07
(DB: external DC braking), 08 (SET: Set
2nd motor data), 09 (2CH: 2-stage accel-
eration/deceleration), 11 (FRS: free-run
stop), 12 (EXT: external trip), 13 (USP:
C002
R/W
unattended start protection), 14: (CS:
commercial power source enable), 15
(SFT: software lock), 16 (AT: analog input
voltage/current select), 18 (RS: reset), 20
(STA: starting by 3-wire input), 21 (STP:
stopping by 3-wire input), 22 (F/R: for-
ward/reverse switching by 3-wire input),
23 (PID: PID disable), 24 (PIDC: PID
C003
R/W
reset, 27 (UP: remote control UP func-
tion), 28 (DWN: remote control DOWN
function), 29 (UDC: remote control data
clearing), 31 (OPE: forcible operation), 32
(SF1: multispeed bit 1), 33 (SF2: multi-
speed bit 2), 34 (SF3: multispeed bit 3),
35 (SF4: multispeed bit 4), 36 (SF5: multi-
speed bit 5), 37 (SF6: multispeed bit 6),
C004
R/W
38 (SF7: multispeed bit 7), 39 (OLR: over-
load restriction selection), 40 (TL: torque
limit enable), 41 (TRQ1: torque limit
selection bit 1), 42 (TRQ2: torque limit
selection bit 2), 44 (BOK: braking confir-
mation), 46 (LAC: LAD cancellation),
47 (PCLR: clearance of position devia-
tion), 50 (ADD: trigger for frequency addi-
C005
R/W
tion [A145]), 51 (F-TM: forcible-terminal
operation), 52 (ATR: permission of torque
command input), 53 (KHC: cumulative
power clearance), 56 (MI1: general-pur-
pose input 1), 57 (MI2: general-purpose
input 2), 58 (MI3: general-purpose input
3), 59 (MI4: general-purpose input 4), 60
(MI5: general-purpose input 5), 61 (MI6:
general-purpose input 6), 62 (MI7: gen-
C006
R/W
eral-purpose input 7), 65 (AHD: analog
command holding), 66 (CP1: multistage
position settings selection 1 ), 67 (CP2:
multistage position settings selection 2),
68 (CP3: multistage position settings
selection 3), 69 (ORL: Zero-return limit
function), 70 (ORG: Zero-return trigger
function), 73 (SPD: speed / position
C007
R/W
switching), 77 (GS1: safety input 1), 78
(GS2: safety input 2), 81 (485: EzCOM),
82 (PRG: executing Drive Programming),
83 (HLD: retain output frequency), 84
(ROK: permission of run command), 85
(EB: Rotation direction detection(for V/f
with ENC), 86 (DISP: Display limitation),
90 (UIO: Unprotected inverter operation),
91 (PSET: preset position), 255 (no).
-
-
Inaccessible
C011
R/W
00 (NO), 01 (NC)
C012
R/W
00 (NO), 01 (NC)
C013
R/W
00 (NO), 01 (NC)
Section B-4
Data
resolution

Hide quick links: