Dc Bus Avr For Deceleration Settings; Sto Setting - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

"B" Group: Fine Tuning Functions
3-6-22 DC Bus AVR (Automatic Voltage Regulation) for Deceleration
Settings
Func.
Code





3-6-23 STO (Safe Torque Off) Setting
Func.
Code

150
This function is to achieve
stable DC bus voltage in case
of deceleration. DC bus volt-
age rises due to regeneration
during deceleration. When
this
function
is
(= or ), inverter con-
trols the deceleration time so
that the DC bus voltage not to
go up to the overvoltage trip
level, and leads to the trip-
less operation during deceler-
ation.
Please note that the actual
deceleration time can be lon-
ger in this case.
"B" Function
Name
Overvoltage protection
tion selection during decelera-
tion
Overvoltage protection level
during deceleration
Overvoltage protection
parameter
Overvoltage protection
proportional gain setting
Overvoltage protection inte-
gral time setting
Please refer to Appendix E Safety (ISO 13849-1) on page 379 for detailed
information.
"B" Function
Name
GS input mode
DC bus voltage
activated
Freq
Description

func-
OFF (Disabled)

V-cnst (DC voltage kept
constant)

Accel (Acceleration enabled)
DC bus voltage of suppression.
Range is:
200 V class 330 to 395
400 V class 660 to 790
Accel. rate when =.
Set range: 0.10 ~ 30.00 sec.
Proportional gain when =.
Range is: 0.00 to 5.00
Integration time when =.
Range is: 0.0 to 150.0
Description
Two option codes:

No trip

Trip
Section 3-6
Threshold voltage to start DC bus AVR ()
DC bus AVR
Normal
operation
Run
Mode
EU
Edit
01
380/
760
1.00
0.20
1.0
Run
Mode
EU
Edit
00
t
t
Defaults
Units
V
sec
sec
Defaults
Units