5-9 Functions Relating to Protections, Warnings and Various Output Signals

Signal During RUN (RUN)

A signal is output by a multi-function output terminal or multi-function relay output terminal
while the Inverter is operating.
This signal turns ON only with Inverter output, and it is not output even when a RUN command
is issued by setting the frequency to 0 Hz. (The RUN lamp is lit when a RUN command is input.)
Allocate "00: RUN (During RUN)" to any Multi-function Output Terminal Selections (C021 to
C022) or Multi-function Relay Output Function Selection (C026).
Also outputs a signal during DC injection braking.
Below is the time chart. The RUN signal will remain ON until the motor stops, even when the
RUN command is turned OFF.