Analog Output Operation; Using For Process Variable Of Pid Control; Simple Positioning By Pulse Train Input - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

Analog Output Operation

4-8
Analog Output Operation
252
When using this mode, you should set
detected by input-capture, and calculated based on the ratio of designated max.
frequency (under 32 kHz). Only an input terminal "EA" will be used in this case.

2. Using for process variable of PID control

You can use the pulse train input for process variable (feedback) of PID control.
In this case you need to set

3. Simple positioning by pulse train input

This is to use the pulse train input like an encoder signal. You can select three
types of operation.
In inverter applications it is useful to monitor the
inverter operation from a remote location or from
the front panel of an inverter enclosure. In some
cases, this requires only a panel-mounted volt
meter. In other cases, a controller such as a PLC
may provide the inverter's frequency command,
and require inverter feedback data (such as output
frequency or output current) to confirm actual oper-
ation. The analog output terminal [AM] serves
these purposes.
The inverter provides an analog voltage output on terminal [AM] with terminal
[L] as analog GND reference. The [AM] can output inverter frequency or cur-
rent output value. Note that the voltage range is 0 to +10 V (positive-going
only), regardless of forward or reverse motor rotation. Use
terminal [AM] as indicated below.
Func.
Code












The [AM] signal offset and gain are adjustable, as indicated below.
Func.
Description

AM gain setting

AM bias setting


to
. In this case the frequency is


to
. Only "EA" input terminal is to be used.
Description
Output frequency
Output current
Output torque
Output voltage
Power
Thermal load rate
LAD frequency
Fin temperature
Output torque <signed>
YA1 (Drive Programming)
Option
Range
50~200
0~100
Section 4-8
AM H
O
OI
L
Analog
+
-
Voltage
A GND
Output
10 VDC
full scale,
1 mA max.
See I/O specs on
page 195

to configure
Default
100
0