Connecting the Inverter to ModBus

B-2
Connecting the Inverter to ModBus
296
Modbus connector is in control terminal block as below. Note that RJ45 con-
nector (RS-422) is used for external operator only.
Dip switch for termination resistor
SN
7
6
5
4
3
SP
EO
EA
H
O
OI
RS-485
(Modbus)
External device
(Master)
-
+
SP
MX2 (No.1)
Terminate Network Wiring – The RS-485 wiring must be terminated at each
physical end to suppress electrical reflections and help decrease transmission
errors. MX2 has a built-in 200 resistor activated by a dip switch. Select termi-
nation resistors that match the characteristic impedance of the network cable.
The diagram above shows a network with the needed termination resistor at
each end.
2
1
L
PLC
P24
L
AM CM2
12
11
SN
SP
SN
MX2 (No.2)
MX2 (No.3)
200 Ω
Section B-2
USB
RS-422
(Operator)
SP
SN
SP
SN
MX2 (No.n)