Inverter Parameter Setup - Omron 3G3MX2 User Manual

Mx2 series 200 v class three-phase input 0.1 to 15 kw 200 v class single-phase input 0.1 to 2.2 kw 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

Connecting the Inverter to ModBus
Func.
Code
A001
Frequency reference selection
A002
Run command selection
C071
Communication speed selection
(Baud rate selection)
C072
Communication station No. Selection
C074
Communication parity selection
C075
Communication stop bit selection
C076
Communication error selection
C077
Communication error timeout
C078
Communication wait time
P200
Serial comms mode
P201 to
Modbus external register 1 to 10
P210
P211 to
Modbus register format 1 to 10
P220
P221 to
Modbus register scaling 1 to 10
P230
P301 to
Modbus internal register 1 to 10
P310
P400
Big/Little endian selection
Inverter Parameter Setup – The inverter has several settings related to
ModBus communications. The table below lists them together. The Required
column indicates which parameters must be set properly to allow communica-
tions. You may need to refer to the host computer documentation in order to
match some of its settings.
Name
Note When you change any of the parameters above, the inverter power must be
rebooted in order to activate new parameters. Instead of rebooting, turning
ON/OFF of reset terminal works as same.
Required
00 Digital operator
01 Terminal
02 Operator
03 ModBus communication
10 Operation function result
01 Terminal
02 Operator
03 ModBus communication
03 2400 bps
04 4800 bps
05 9600 bps
06 19.2 k bps
07 38.4 k bps
08 57.6 k bps
09 76.8 k bps
10 115.2 k bps
Network address, range is 1 to 247
00 No parity
01 Even
02 Odd
Range is 1 or 2
00 Trip
01 Decel-Trip (Trip after deceleration stop)
02 Ignore
03 Free-RUN (Free-run stop)
04 Decel-Stop (Deceleration stop)
Comm. Watchdog timer period,
range is 0.00 to 99.99 sec.
Time the inverter waits after receiving a
message before it transmits.
Range is 0 to 1000 ms
00 Standard
01 Free mapping
Range is 0000h to FFFFh
00 Unsigned
01 Signed
Range is 0.001 to 65.535
Range is 0000h to FFFFh
00 Big endian
01 Little endian
02 Special endian
Section B-2
Settings
297