Wiring Block Diagram - Avaya S8700 Installation Instructions Manual

Installing an avaya s8700 media server with an avaya g650 media gateway
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Wiring Block Diagram

These alarms then should be tested using the
Testing
follows:
#
Signal
1
BOD2
2
ACF2
3
BIF2
4
RFA2
104
Port
Alarm Type
01major
minor
01 minor
minor
01C0901
minor
01C0902
minor
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
test eda-external-device-alarm all
Alt Name
(7 char. limit)
Test to bring in alarm.
BatChg
Remove AC power by turning
off the equipment room breaker
for the GMCC.
AC
Remove AC power by turning
off the equipment room breaker
for the GMCC.
BIU
Unplug the -48VDC BATT
connector this will cause the
BNA LED to come on and the
BIU to alarm.
RECT
Unplug rectifiers one at a time
until this alarm comes in
indicating you no longer have
N+1 sparing of rectifiers for
your load.