Avaya S8700 Installation Instructions Manual page 99

Installing an avaya s8700 media server with an avaya g650 media gateway
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Figure 19: Typical media gateway grounding wiring diagram
Figure notes
1
Media Gateway
2
Media Gateway Ground Terminal
Block
3
6 AWG (#40) (16 mm
Gateway GROUND Wire
4
Single-Point Ground Block
Connecting remote power off cable, if required
Part 1,
on page 100 shows the location of the Remote Power Off (RPO) cable. The opposite end of the
cable connects to the Emergency Power Off (EPO) switch located for the equipment room.
Even though the equipment room EPO switch disconnects main AC power to the equipment room, it
cannot disconnect the battery power from the J58890CH. An auxiliary set of contacts inside the EPO are
used for this function.
1
Plug the RPO cable into the connector shown in
— Part 2,
2
Route the opposite end of the wires to the EPO switch. The opposite end of the RPO cable
connects to the internal relay.
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
1
2
2
) Media
on page 101.
NOTE:
The EPO switch and the auxiliary contacts (inside the EPO switch assembly) are
customer-provided.
5
6
4
3
widfspg2 KLC 091603
5
6 AWG (#40) (16 4 mm
Approved Ground
6
AC Load Center Single-Point Ground
7
Approved Ground
8
Over 50 ft. (15.2 m)
Figure 20, Remote power off cable connections —
Figure 21, Remote power off cable connections
7
8
2
) Ground Wire to
99

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G650

Table of Contents