Figure 18: Power distribution unit (J58890CH)
f001c LAO 091103
Figure notes
1
Ground Terminal Block
Grounding to an AC load center more than 50 feet (15.2 meters)
from media gateway
1
Mount the single-point ground block to any surface between the media gateways and the AC load
center single-point ground. The single-point ground block must be mounted to a non-metallic
surface.
2
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
GROUND wire to the media gateway ground block. See
grounding wiring diagram,
3
Route the opposite end of the wire to the single-point ground block and connect.
4
At the next media gateway, connect a 6 AWG (#40) (16 4 mm
the media gateway ground block.
5
Repeat connecting each media gateway to the single-point ground block.
6
Connect a 6 AWG (#40) (16 mm
block.
7
Route the ground wire to the AC load center ground and connect.
98
on page 99.
NOTE:
If a media gateway is located remotely (in a separate room or building), route the media
gateway GROUND wire to an approved protective ground.
2
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
2
To AC load center or approved single-
point ground block
Figure 19, Typical media gateway
) ground wire to an unused terminal on the single-point ground
1
2
2
) media gateway
2
) media gateway GROUND wire to
December 2003