Avaya S8700 Installation Instructions Manual page 103

Installing an avaya s8700 media server with an avaya g650 media gateway
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

Figure 23: J58890CH Global AC Input Power Distribution Unit
J58890CH
Global AC input
Power distibution unit
Wiring these alarms back into the system as external device alarms allows remote alarming of the
following:
1
Batteries on Discharge (BOD2): The system is running on batteries do to an AC input power
failure or an insufficient number of rectifiers to carry the cabinet load. The BIU's "BOD" LED. is
on.
2
AC input power failure (ACF2). The system is running on batteries.
3
Battery Interface Unit Failure (BIF2): This indicates a battery interface unit failure (all BIU
L.E.D.s may be off), a battery temperature warning (BIU's "BTW" LED. is on), or a battery not
available alarm (BIU's "BNA" LED. is on).
4
Rectifier Failure Alarm (RFA2): This indicates that at least one rectifier has failed. The defective
rectifier should have the red "FAULT" LED. on.
Administration
1
command
with sample naming as follows:
#
Signal
1
BOD2
2
ACF2
3
BIF2
4
RFA2
1The System Parameters Customer-Options screen must have the
field set to yes.
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
These alarms then should be administered using the
Port
Alarm Type
01major
minor
01 minor
minor
01C0901
minor
01C0902
minor
BOD2+
BOD2-
ACF2+
ACF2-
BIF2+
BIF2-
RFA2+
RFA2-
add eda-external-device-alarm
Alt Name
(7 char. limit)
Description
BatChg
GMCC Batteries are Charging
AC
GMCC AC input power
BIU
GMCC BNA, BTW, and BIU
RECT
GMCC Rectifiers
External Device Alarm Admin
103