Connecting optional external alarm cable
1
Plug the external alarm cable into the connector shown in
connection,
2
Route the opposite end of the cable to the MDF.
Figure 29: External alarm cable connection
sdf001c LAO 091103
Figure notes
1
Ground Terminal Block
MCC1 on long-term battery holdover alarm
cabinet option requires connecting 1 of the J58890CH Power Distribution Unit alarm pairs to the Minor
Alarm pair on the AUX connector. This will provide an alarm indicating that AC has failed and that there
are a limited number of hours before the batteries will be discharged and the system will shut off.
This then should be administered as a minor alarm using the
command (for cabinet #01)
The Alt Name given to the alarm should be "AC".
The
Description
2The System Parameters Customer-Options screen must have
field set to yes.
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
on page 111.
2
.
field should be
GMCC AC input power
Figure 29, External alarm cable
2
To AC load center or approved single-
point ground block
The MCC1 with the large (long term holdover) battery
add eda-external-device-alarm 01minor
.
External Device Alarm Admin
1
2
111