Avaya S8700 Installation Instructions Manual page 119

Installing an avaya s8700 media server with an avaya g650 media gateway
Hide thumbs Also See for S8700:
Table of Contents

Advertisement

6
At the AC load center, connect a 10 AWG (#25) (6 mm
This ground wire will later be tie-wrapped to the trunk cables and connected to the Coupled
Bonding Conductor (CBC) ground block at the main distribution frame (MDF).
The coupled bonding conductor (CBC) wires are installed and terminated in
coupled bonding conductor
Figure 33: Typical media gateway ground location
Figure notes
1
Media Gateway
2
Media Gateway Ground Terminal
Block
3
6 AWG (#40) (16 mm
Gateway GROUND Wire
Grounding an AC load center more than 50 feet (15.2 meters)
from media gateway
1
Mount the single-point ground block to any surface between the media gateways and the AC load
center single-point ground. The single-point ground block must be mounted to a non-metallic
surface.
2
At the bottom rear of the first media gateway, connect a 6 AWG (#40) (16 mm
GROUND wire to the media gateway ground block. See
ground location,
3
Route the opposite end of the wire to the single-point ground block and connect.
Installing the Avaya S8700 Media Server with an Avaya G650 Media Gateway
December 2003
on page 172.
4
1
2
2
) Media
on page 97.
2
) wire to the single-point ground block.
6
3
5
widmgrn2 KLC 091603
4
AC Load Center
5
Less than 50 Wire feet (15.2 m)
6
Approved Ground
Figure 17, Typical media gateway
Installing the
2
) media gateway
119

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

G650

Table of Contents