Description of Functions and Constants

2-8-14 Multifunction Contact Input Function Selection

Item name
Multifunction contact input function
Local/Remote
Operation
The function of external output terminals 4 and 5 can be changed if
necessary. Set No. 32 and No. 33 in the descending order.
Terminal 4 function: set No. 32.
Terminal 5 function: set No. 33.
Set value
0 (see note 1) FWD/REV run command
1 (see note 2) External fault (NO contact input)
2
3 (see note 3) Multi-step speed reference 1
4
5
6
7
8
9
10
11
12
14 (see note
4)
Note
1. "0" can be set only to No. 32.
2. Factory preset value for No. 32
3. Factory preset value for No. 33
4. "14" can be set only to No. 33.
5. Contact input capacity is 24 VDC 8 mA or less. Circuit leakage
current at signal OFF must be 100 mA or less.
Terminal function at 3-WIRE sequence selection:
1
Run command (run at "closed")
2
Stop command (stop at "open")
4
FWD/REV run selection
6
(FWD run at "open", REV run at "closed")
No. 1 must first be set to 0000 or 0001. If terminal 4 or 5 is closed,
local operation from the Digital Operator is in effect. If terminals 4
and 5 are open, remote operation from the external terminals is in
effect. Inverter operation must be stopped before switching from
remote to local operation, otherwise the serr is displayed. The
Inverter operation, however, is not be affected by the serr mes-
sage.
Constant to be set
No. 32 and No. 33
(3-WIRE sequence selection)
External fault (NC contact input)
Multi-step speed reference 2
JOG command
Accel/Decel time select
External baseblock (NO) contact input
External baseblock (NC) contact input
Search command from maximum frequency
Search command from setting frequency
Accel/Decel prohibit command
Local/Remote operation
UP/DOWN command
3G3XV
Section 2-8
Factory preset
No. 32 =1, No. 33 = 3
Function
53