Complete the following steps:
1. Check the CMM or FSM event log for any fan- or cooling-related issues or power-related issues..
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• 806f0a07-2584ffff : [ProcessorElementName] is operating in a Degraded State.
Processor(s) ares being throttled due to thermal or power conditions.
May also be shown as 806f0a072584ffff or 0x806f0a072584ffff
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - CPU
SNMP Trap ID
42
CIM Information
Prefix: PLAT ID: 0038
User Response
Complete the following steps:
1. Check the CMM or FSM event log for any fan- or cooling-related issues or power-related issues..
2. Make sure that the airflow at the front and rear of the chassis is not obstructed and that fillers are
in place and correctly installed.
3. Make sure that the room temperature is within operating specifications.
• 806f0a0c-2001ffff : An Over-Temperature Condition has been detected on the
[PhysicalMemoryElementName] on Subsystem [MemoryElementName].
An over temperature condition for memory has been detected.
May also be shown as 806f0a0c2001ffff or 0x806f0a0c2001ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
Lenovo Flex System x440 Compute NodeInstallation and Service Guide