Disconnecting A Power Input Cable From A Terminal Block - Nortel Passport 15000 Hardware Installation And Maintenance

Hide thumbs Also See for Passport 15000:
Table of Contents

Advertisement

Disconnecting a power input cable from a terminal block

Prerequisites
Procedure steps
Passport 15000, 20000 Hardware Installation, Maintenance, and Upgrade
Disconnect a power input cable to a terminal block of a polyvalent or an ETSI
power-and-ground assembly from the power source to replace the cable or as
part of replacing the assembly.
You must be familiar with "Safety considerations and best practices"
(page 53).
When disconnecting a power input cable to replace it, you need one of
equal specifications or better. Install the cable in parallel to the existing
cable from the source up to the power-and-ground assembly.
1
Switch off all breakers or remove all fuses that enable power to that
branch of cable. Put tape over the breakers or fuse openings to indicate
deliberate disablement.
2
Switch off all breakers (press O in) on the BIM that is fed by that cable.
Refer to the figures "Overhead power input cables for the lower shelf
connected to the BIP" (page 337) and "BIMs for specific shelf nodes"
(page 352). Switching a breaker off generates a software alarm. This is
normal during a replacement.
3
Unfasten the large slotted captive screw in the terminal block in which the
cable is connected.
4
Ensure that the power input cable is labelled to enable its appropriate re-
connection or the connection of a replacement cable.
5
Repeat step 1 to step 4 for each other power cable that is to be
disconnected.
Chapter 17 Hardware procedures 347
5.2S2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Passport 20000

Table of Contents