P1 - 26
Reserved
P1 - 27
Reserved
P1 - 28
Reserved
P1 - 29
Reserved
P1 - 30
Reserved
P1 - 31
Reserved
P1 - 32
LSTP

Motor Stop Mode Selection

Default: 0
Applicable Control Mode: P/S/T
Unit: N/A
Range: 0 ~ 11
Settings: This parameter is used to select servo motor stop mode.
ASD-PU-01A
• Fault Stop Function Settings:
When a fault occurs (except for CWL, CCWL, EMGS and serial communication error), it is
used to set servo motor stop mode.
0: Stop instantly
1: Decelerate to stop
• Dynamic Brake Activation Settings:
When a fault occurs (except for CWL, CCWL, EMGS and serial communication error), the
servo drive will turn on (Servo On) and then off (Servo Off) automatically.
0: Use dynamic brake when Servo Off (the servo drive is disabled).
1: Allow servo motor to coast to stop when Servo Off (the servo drive is disabled).
Revision January, 2009
Chapter 7 Servo Parameters|ASDA-B Series
Communication Addr.: 011AH
Communication Addr.: 011BH
Communication Addr.: 011CH
Communication Addr.: 011DH
Communication Addr.: 011EH
Communication Addr.: 011FH
Communication Addr.: 0120H
Related Section: N/A
ASD-PU-01B
7-31