• Using V/f Control Mode

Vector control mode is preset at the factory.
Control mode selection (n002): 0: V/f control mode (initial setting)
Adjusting torque according to application
Adjust motor torque by using "V/f pattern" and "full-range automatic torque boost".
• V/f pattern setting
Set V/f pattern by n011 to n017 as described below. Set each pattern when using a
special motor (high-speed motor, etc.) or when requiring special torque adjustment
of machine.
n016 n014 n013
Parameters
No.
n011
Max. output frequency
n012
Max. voltage
Max. voltage output frequency
n013
(base frequency)
n014
Mid. output frequency
n015
Mid. output frequency voltage
n016
Min. output frequency
n017
Min. output frequency voltage
* 10.0V for 200V class 7.5/10hp (5.5/7.5kW)
20.0V for 400V class 7.5/10hp (5.5/7.5kW)
NOTE: Values with parentheses indicate 400V class.
40
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
1: Vector control mode
Be sure to satisfy the following
conditions for the setting of n011
to n017.
n016 < n014 < n013 < n011
If n016 = n014 is set, the set
value of n015 is disabled.
n011
(frequency)
Name
Unit
Setting range
0.1Hz
50.0 to 400.0Hz
1 to 255.0V
1V
(0.1 to 510.0V)
0.1Hz
0.2 to 400.0Hz
0.1Hz
0.1 to 399.9Hz
0.1 to 255.0V
1V
(0.1 to 510.0V)
0.1Hz
0.1 to 10.0Hz
1 to 50.0V
1V
(0.1 to 100.0V)
Initial Setting
60.0Hz
230.0V
(460.0V)
60.0Hz
1.5Hz
12.0V
(24.0V)
1.5Hz
4.3V *
(8.6V)