Chapter 8 Servo Parameters
P5 - 15 
PMEM
Default: 0x0
Applicable Control Mode: ALL
Unit: N/A
Range: 0x0 ~ 0x0011
Data Size: 16-bit
Display Format: Hexadecimal
Settings:
This parameter is designed for the users who need to change the positioning point
frequently via communication.
Display
Range
X=0: The data of PATH 1 (P6-02 ~P6-03) will be retained (memorized) when the power
goes off.
X=1: The data of PATH 1 (P6-02 ~P6-03) will not be retained (memorized) when the
power goes off.
Y=0: The data of PATH 2 (P6-04 ~P6-05) will be retained (memorized) when the power
goes off.
Y=1: The data of PATH 2 (P6-04 ~P6-05) will not be retained (memorized) when the
power goes off.
Other settings: Reserved
P5 - 16 
AXEN
Default: 0
Applicable Control Mode: ALL
Unit: PUU (user unit)
Range: -2147483648 ~ +2147483647
Data Size: 32-bit
Display Format: Decimal
Settings:
Read function: This parameter is used to read the actual position of the motor encoder,
i.e. the monitor variable V000 + deviation value.
Write function (available in firmware V1.015 and later models only):
The users can write any value and doing this will no change the value of monitor
variable V000 and will not affect the position coordinate either.
8-130
Call 1(800)985-6929 for Sales
deltaacdrives.com
PATH 1 ~ PATH 2 Data Not Retained Setting
0
0
-
-
Axis Position: Motor Encoder
deltaacdrives.com
Related Section: N/A
Y
X
0 ~ 1
0 ~ 1
Related Section: Section 7.3
sales@deltaacdrives.com
Address: 051EH, 051FH
Address: 0520H, 0521H
Revision January 2011