6.3.7 Resonance Suppression
The resonance of mechanical system may occur due to excessive system stiffness or
frequency response. However, this kind of resonance condition can be improved,
suppressed, even can be eliminated by using low-pass filter (parameter P2-25) and notch
filter (parameter P2-23, P2-24) without changing control parameter.
Relevant parameters:
P2 - 23
NCF1
Default: 1000
Applicable Control Mode: ALL
Unit: Hz
Range: 50 ~ 1000
Data Size: 16-bit
Display Format: Decimal
Settings:
This parameter is used to set first resonance frequency of mechanical system. It
can be used to suppress the resonance of mechanical system and reduce the
vibration of mechanical system.
If P2-24 is set to 0, this parameter is disabled.
The parameters P2-23 and P2-24 are the first group of notch filter parameters and
the parameters P2-43 and P2-44 are the second group of notch filter parameters.
P2 - 24
DPH1
Default: 0
Applicable Control Mode: ALL
Unit: dB
Range: 0 ~ 32
Data Size: 16-bit
Display Format: Decimal
Settings:
This parameter is used to set magnitude of the resonance suppression that is set
by parameter P2-23. If P2-24 is set to 0, the parameters P2-23 and P2-24 are both
disabled.
The parameters P2-23 and P2-24 are the first group of notch filter parameters and
the parameters P2-43 and P2-44 are the second group of notch filter parameters.
Revision January 2011
Call 1(800)985-6929 for Sales
deltaacdrives.com
Notch Filter 1 (Resonance Suppression)
Notch Filter Attenuation Rate 1
(Resonance Suppression)
deltaacdrives.com
sales@deltaacdrives.com
Chapter 6 Control Modes of Operation
Address: 022EH, 022FH
Related Section:
Section 6.3.7
Address: 0230H, 0231H
Related Section:
Section 6.3.7
sales@deltaacdrives.com
6-37