Communication with the PLC
6.3.2
Start single measurement via process channel
Measurement start
Sensor selection A/B
Sensor selection A/B
OUT 0 to OUT 2 + OUT 4
(Warning, 0-sheet, 1-sheet, 2-sheet)
(Warning, 0-sheet, 1-sheet, 2-sheet)
Fig. 43: Start single measurement via process channel
t
:
System reaction time = Measuring time ( see chapter 2.4)
s
1)
In case of "Function fault" = 1 "Function result" will sometimes remain at 0.
Waiting for "Function fault"
In case of "Function fault":
- Pause 100 ms
- Set "Measurement start" to LOW
- Reset "Function fault"
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
82
Double Sheet Detector R1000 series E20
with integrated fieldbus interface
BIN 10.6 to 10.7
BIN 10.6 to 10.7
BOUT 8.0
1)
Function result
BOUT 8.2
Function fault
BOUT 8.3
Ready
BOUT 8.4 to 8.7
Set "Measurement start" to HIGH
Manual
"1" in case of fault
"0" in case of fault
„0" active
„0" active
t
< 5ms
s
or
Waiting for "Function result"
In case of "Function result":
- Analyse
- Set "Measurement start" to LOW
B0046191 / Rev. 1.12
< 10ms