3.4.1
System parameters
"Language"
System languages available for operating the unit via display and keyboard:
German
English
Spanish
Italian
French
"Dimension"
Switches the indication of the thickness values on the display between mm  inch.
"Bus readout"
Switches the out feeding of the thickness values via Field bus between mm  inch.
"Bus address"
Sets the bus address, as far as a participant address is required for Field bus. Value range 1...125
"Baud rate Field bus"
Sets the Baud rate of the Field bus (as far as required for the Field bus).
In case off EtherNet/IP: DHCP/IP/SUBNET/GATEWAY
"CLR parameter (Clear Program Parameter)"
Deletes all program parameters. For doing so, the parameter needs to be set to "yes". Executing
the command requires several minutes, since the program memory will completely cleared. All
program parameters will be reset to the default values and existing teach-in data will be deleted.
Using this function only makes sense if a unit is to be newly used for another machine.
"Measurement fast/normal"
For time-critical applications the measuring time can be slightly shortened for measuring FE
material. If "fast" is selected and double sheet occurs, the measuring is terminated on reaching the
upper switch limit, and the information "2-sheet" is released. If "normal" is selected, the measuring
will be executed to the end and the measured thickness will be displayed.
"Password yes/no"
Switches the password request on/off. If the password request is set "on", the system / program
parameters can only be changed after the password has been entered.
"Sensor type"
At the time of editing the sensor types P30, P36, P42, P42A, P75, P75V and P128 are available.
For this sensor a characteristically curve for linearization purposes exists.
"Number of sensors"
Defines the number of connected sensors. Those sensors are then available for measuring
(only for 4P-Version).
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
Double Sheet Detector R1000 series E20
with integrated fieldbus interface
Manual
System description
29

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

E20

Table of Contents