General Site Guidelines for Installing the SRX210 Services Gateway

Related
Documentation

SRX210 Services Gateway Cabinet Requirements

Copyright © 2012, Juniper Networks, Inc.
The following precautions help you plan an acceptable operating environment for your
SRX210 Services Gateway and avoid environmentally caused equipment failures:
For the cooling system to function properly, the airflow around the chassis must be
unrestricted. Allow sufficient clearance between the front and back of the chassis and
adjacent equipment. Ensure that there is adequate circulation in the installation location.
Follow the ESD procedures to avoid damaging the equipment. Static discharge can
cause components to fail completely or intermittently over time.
Ensure that the blank Mini-PIM panel is installed in the empty slot to prevent any
interruption or reduction in the flow of air across internal components.
NOTE:
Install the device only in restricted areas, such as dedicated
equipment rooms and equipment closets, in accordance with Articles
110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.
SRX210 Services Gateway Specifications on page 7
SRX210 Services Gateway Safety Requirements, Warnings, and Guidelines on page 52
SRX210 Services Gateway Cabinet Requirements on page 39
SRX210 Services Gateway Rack Requirements on page 40
Site Preparation Checklist for the SRX210 Services Gateway on page 37
Clearance Requirements for Airflow and Hardware Maintenance of the SRX210 Services
Gateway on page 41
The SRX210 Services Gateway can be installed in a standard 800 mm (31.5 in.) or larger
enclosed cabinet.
Table 17 on page 39
and airflow requirements.

Table 17: SRX210 Services Gateway Cabinet Requirements

Cabinet
Requirements
Specifications
Cabinet size
19 in. (48.3 cm) as defined in Cabinets, Racks, Panels, and Associated
Equipment (document number EIA-310–D) published by the Electronics
Industry Association (
You can mount the services gateway horizontally in the cabinet.
provides the details on cabinet size, clearance,
http://www.eia.org
).
Chapter 6: Site Preparation
39