Basic information about the drive system
14.12 System rules, sampling times and DRIVE-CLiQ wiring
Parameters used
● p0097
● p9910
● p9940
● p0151
● p3801
● p1200
14.12.5.4

Changing the offline topology in the STARTER commissioning tool

You can change the device topology in the Startdrive commissioning tool by shifting the
components in the topology tree. Please refer to SINAMICS S120 Commissioning Manual and
the Startdrive online help for details and examples.
14.12.5.5

Modular machine concept: Offline correction of the reference topology

The topology is based on a modular machine concept. The machine concept is created
OFFLINE in the Startdrive commissioning tool in the maximum version as reference topology.
The maximum version is the maximum expansion of a particular machine type. In the maximum
version, all the machine components that can be used are pre-configured in the reference
topology.
Deactivating components/handling non-existent components
In a lower expansion stage of the machine, you must mark drive objects and encoders that are
not used in the Startdrive topology. To do this, for the corresponding drive objects and encoder,
set parameter p0105 or p0145 = 2 (deactivate component and does not exist). Components set
to the value "2" in a project generated OFFLINE must never be inserted in the actual topology
at all.
If a component fails, the sub-topology can also be used to allow a machine to continue to
operate until the spare part is available. In this case, however, no BICO source must be
interconnected from this drive object to other drive objects.
Example of a sub-topology
The starting point is a machine created OFFLINE in the Startdrive commissioning tool. "Drive
1" was not implemented for this machine.
1. You can remove drive object "Drive 1" "OFFLINE" from the reference topology using
p0105 = 2.
2. Change over the DRIVE-CLiQ cable from the Control Unit directly to "Drive 2".
852
Select drive object type
Target topology accept additional components
Configuration auto commissioning (p0097 / p9910)
Voltage Sensing Module component number
Sync-line-drive drive object number
Flying restart operating mode
Function Manual, 06/2019, 6SL3097-5AB00-0BP2