8.21.8

"Tolerance band pulse number" monitoring

Overview
The function extension "Tolerance band pulse number monitoring" monitors the number of
encoder pulses between two zero marks. An alarm is output if the number lies outside a
tolerance band that can be selected.
Commissioning the function
Carry out the following steps to start the function:
1. Set parameter p0437.2 = 1 to activate the monitoring.
2. Using parameters p4683 and p4684, set the upper and the lower limits of the tolerance
band. Within this tolerance band, the detected number of pulses is considered to be correct.
Further information on the procedure
● After each zero mark, it is again checked as to whether the number of pulses up to the next
zero mark lies within the tolerance band.
● Display of uncorrected encoder pulses
For p0437.7 = 1, the number of corrected pulse errors is displayed in r4688 with the correct
sign. Set p0437.7 = 0 in order to indicate the corrected pulse errors per zero mark distance
in r4688.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
If ...
If the pulse number lies outside of the tolerance
band and the function "Pulse number correction
for faults" is parameterized via p0437.2 = 1, ...
If one of the limits has a value of 0, ...
If ...
If the tolerance band limit is not reached during a
drift after a revolution, ...
If the zero mark is exceeded; ...
8.21 Tolerant encoder monitoring
Then ...
then alarm A3x422
is output for 5 seconds.
1)
then alarm A3x4221) is deactivated.
Then ...
an alarm is not output.
a new measurement is performed.