To ensure that the function works for more than one drive at the same time, the terminals for the
corresponding drives must be grouped together as follows:
1. Switch-off signal path
Connect the p9620 parameters of all drives that belong to a group with a single DI (r0722.x)
of the CU320‑2.
2. Switch-off signal path (Motor Module / Power Module with CUA3x)
Wire the terminals for the individual Motor Modules/Power Modules, belonging to the group,
with CUA31/CUA32.
Note
Parameterization of the grouping
The grouping must be configured (DI on Control Unit) and wired (EP terminals) identically in
both monitoring channels.
Note
Response of STO for grouping
If a fault in a drive results in a "Safe Torque Off" (STO), this does not automatically mean that
the other drives in the same group also switch to "Safe Torque Off" (STO).
The assignment is checked during the test for the switch-off signal paths. The operator selects
"Safe Torque Off" for each group. The check is drive-specific.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
11.8 Controlling via terminals on the Control Unit and Motor/Power Module
Safety Integrated Basic Functions