Servo control

5.21 Variable signaling function

5.21
Variable signaling function
Function description
Using the "Variable signaling" function, BICO interconnections and parameters that have the
attribute "traceable" can be monitored; otherwise they can also be recorded using the "Device
trace" commissioning function.
Note
The variable signaling function works with an accuracy of 8 ms. This value must also to be taken
into account for pickup and dropout delay.
Enter the desired data source into parameter p3291 of the drive object expert list. In parameter
p3295 define a threshold value for the data source. The hysteresis of the threshold value can
be set with p3296. If the threshold value is violated, then an output signal is generated from
r3294. A pickup delay can be set with p3297 and a dropout delay with p3298 for the output
signal r3294.
The setting of a hysteresis results in a tolerance band around the threshold value. If the upper
band limit is exceeded, the output signal r3294 is set to "1", if it drops below the lower band limit
the output signal is set to "0"
You set the sampling time of the variable signaling function in p3299.
After completing the configuration, activate the variable signaling function with p3290.0 = 1.
Example 1: switching on temperature-dependent heating
Heating should be switched on depending on the temperature. For this the analog signal of an
external sensor is connected with the variable signaling function. A temperature threshold and
a hysteresis is defined to prevent the heating from switching on and off constantly.