Copy RAM to ROM
You can initiate the saving of all parameters to the non-volatile memory (memory card) in the
drive object Control Unit:
● Press the P key for 3 seconds.
OR
● p0009 = 0
● p0977 = 1
Note
This parameter is not accepted if an identification run (e.g. motor data identification) has
been selected on a drive.
Identification via LED
The main component of a drive object (e.g. Motor Module) can be identified using the index of
p0124. The "Ready" LED on the component starts to flash. The index matches the index in
p0107. The drive object type can be identified via this parameter.
On the drive objects, the components can also be identified via the following parameters:
● p0124 Power unit detection via LED
● p0144 Voltage Sensing Module detection via LED
● p0144 Sensor Module detection via LED
Acknowledging faults
To acknowledge all the faults that have been rectified, press the "FN" key.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
A.4 Parameterization using the BOP20
Appendix
895