8.21.1

Encoder track monitoring

Overview
For square-wave encoders with push-pull signals, the function extension "Encoder track
monitoring" monitors encoder tracks A/B ↔ -A/B, as well as R ↔ -R. The encoder track
monitoring monitors the most important properties of the signals (amplitude, offset, phase
position).
Commissioning the function
Before you activate encoder track monitoring, you must set the following parameters as
specified:
Setting
p0404.3 = 1
p0405.0 = 1
Set p0405.2 = 1 to activate the function.
If you selected your encoder from the list of parameter p0400, then the values above are pre-
selected and cannot be changed (also refer to the information on p0400 in the SINAMICS S120/
S150 List Manual).
Deactivating track monitoring
If encoder track monitoring is activated, you can deactivate the function by setting p0437.26 = 1.
Evaluate messages
All of the track monitoring functions can be individually evaluated. You can use both HTL as well
as TTL encoders.
Drive functions
Function Manual, 06/2019, 6SL3097-5AB00-0BP2
,
Reaction
Switches to the square-wave encoder.
Sets the signal to bipolar.
Basic functions
8.21 Tolerant encoder monitoring
369